| Source |
Public Power Corporation (PPC) |
| Power Supply Voltage |
20 kV, 3Ö, 50Hz |
| Power Supply Points |
30 |
| Power Distribution |
70 mm2, copper cable |
| Rectifier types |
12-pulse rectifiers with silicon diodes |
| Number of substations |
10 (Line2) 10 (Line 3) 2 (Depot) 22 in Total |
| Average spacing |
1100m (Line 2) 1200m (Line 3) |
| Power |
3 MW |
| Overloading capacity |
150% for 2 h 300% for 1 min |
| Output voltage (nominal) |
750 VDC |
| Third Rail |
60 Kg/m, low carbon content steel 17.3 Kg/m, Composite (Aluminum / Stainless Steel) |
| Nominal voltage |
750 VDC |
| Minimum voltage |
525 VDC |
| Maximum voltage |
900 VDC |
| Capacity design |
6-car Trains, 100s Headway |
| Sectionalization |
The entire third rail of the Main Lines: • Line 2 - 18 sections • Line 3 - 14 sections |
| Monitoring & Control |
Remote Control (Syntagma) Local Control Emergency plungers every 200m
|